Thermal hazards due to electric fault arcing Guide for selecting Personal protective equipment (DGUV Information 203-077)
Thermal hazards due to electric fault arcing Guide for selecting Personal protective equipment (DGUV Information 203-077)
Anhangteil
Annex 6 – Exemplary work locations for determining transmission factor kT

Fig. A 6-1
Working on a house junction box: k T = 1.0

Fig. A 6-2
Replacement of a fuse panel in a control cabinet (close to the side wall): k T = 1.0

Fig. A 6-3
Working on a cable distribution cabinet: k T = 1.5

Fig. A 6-4
Working on a compact station: k T = 1.7

Fig. A 6-5
Installing cable sleeves: k T = 1.9

Fig. A 6-6
Working on an electricity pole: k T = 2.4