Appendix 1 - Examples of risk assessment documentation

g_bu_2075_as_1.jpgBG ETEM
Energie Textile Elektro
Medienerzeugnisse
Risk assessment - DocumentationFilling and refilling of SF6 gas compartments as well as recovery of non-contaminated SF6

Please note:Entries in italics are sample texts that you can edit to meet your needs.

Dokumentation
Prepared by: ......................... Responsible Person: .........................
Status as of: ......................... Expert consultation: .........................
Work area:Electrical service location
Work task:Filling and refilling of SF6 gas compartments as well as revcovery of non-contaminated SF6
Description of work tasks

Connecting SF6 servicing units and/or SF6 gas containers to the filling unit in SF6 gas compartments; checking all connections and lines for secure seating; execution of the filling process; removal of the filling equipment. Recovering the SF6 gas using the SF6 gas servicing unit; venting and opening the gas compartments; performing maintenance and upgrade work or work upon conclusion of piece or type testing.

Hazardous substances used/released
DesignationLabelling / H statementsQuantity
SF6Gases under pressure, liquefied gas; H280Quantity used varies according to the filling process Released quantities (only with leaks) in small amounts
Assessment

Risk due to inhalation

There is no exposure to SF6 when properly performed.

In the event of leakage, it cannot be ruled out that small amounts of SF6 will be released. The workplace limit value for SF6 is reliably maintained. The small quantities involved will not lead to a health risk.

Risk due to contact with the skin

Not applicable

Physical-chemical and other hazards

A displacement of oxygen by SF6 is not anticipated.

Protective measures/Effectiveness
Protective measures/checkpointsResponsibility (deadline)Effectiveness/verification
For technical reasons, another substance cannot be substituted.Employer
Utilization of the SF6 gas servicing unit, type ______, manufacturer ______, and/or the SF6 filling unit, type ______, manufacturer ______, according to the specifications provided by the equipment manufacturer, as well as provided by the SF6 switchgear and/or the SF6 operating equipment manufacturer(s).Person responsible for work, all employees
Compliance with smoking, eating and drinking restrictionsEmployee
Compliance with restrictions related to work involving a significant heat build-upPerson responsible for work, all employees
Operating instructions are availableEmployer
Instruction and consultation on occupational medicine and toxicological mattersEmployer, annually
Applied directives, regulations and information

German Ordinance on Hazardous Substances (Gefahrstoffverordnung, GefStoffV)

TRGS 400 German Technical Rule for Hazardous Substances "Risk assessment for activities involving hazardous substances" (Gefährdungsbeurteilung für Tätigkeiten mit Gefahrstoffen) DGUV Information "SF6 Switchgear and Equipment" ("SF6 -Anlagen und -Betriebsmittel", DGUV Information 213-013)

Technical Report IEC 62271-303, Annex D

g_bu_2075_as_1.jpgBG ETEM
Energie Textile Elektro
Medienerzeugnisse
Risk assessment - DocumentationWork related to SF6 gas compartments that may contain SF6 decomposition products

Please note:Entries in italics are sample texts that you can edit to meet your needs.

Dokumentation
Prepared by: ......................... Responsible Person: .........................
Status as of: ......................... Expert consultation: .........................
Work area:Electrical service location
Work task:Work related to SF6 gas compartments that may contain SF6 decomposition products
Description of work tasks

Recovery of SF6 gas using the SF6 gas servicing unit

Ventilation and opening of the gas compartments

Removal of solid decomposition products using an industrial vacuum cleaner or manually using water-free cleaning agents or cleaning products

Performance of maintenance and upgrade work

Hazardous substances used/released
DesignationLabelling / H statementsQuantity
SF6Gases under pressure, liquefied gas; H280Quantity utilized varies according to the filling process Released quantities (only with leaks) in small amounts
Gaseous and solid decomposition productsDecomposition products can be poisonous, causing a hazard to health, irritation or chemical burnsReleased quantity varies according to application and damage involved
Cleaning agent 3% Na2 CO3 solutionRefer to the safety data sheet, section 5.2/10.6Approx. 2 litres
Assessment

Risk due to inhalation

The inhalation of SF6 and SF6 decomposition products cannot be excluded.

A risk ensues when removing solid decomposition products (switching dust), which can lead to lung damage.

A chemical reaction can result in the release of gasses such as hydrogen fluoride (HF) and sulphur dioxide (SO2 ) when opening a gas compartment. For this reason, short-term exposure may be greater than the working limit value.

Risk due to contact with the skin

Contact with skin may cause irritation or acid burns. A moderate risk exists from skin contact according to TRGS 401.

Physical-chemical and other hazards

A risk of suffocation may ensue due to a displacement of oxygen if a residual quantity of SF6 escapes from the switchgear into the working environment.

Protective measures/Effectiveness
Protective measures/checkpointsResponsibility (deadline)Effectiveness/verification
For technical reasons, another substance cannot be substituted.Employer
Utilization of the SF6 gas servicing unit, type ______, manufacturer ______, according to the specifications provided by the equipment manufacturer, as well as provided by the SF6 switchgear and/or the SF6 operating equipment manufacturer(s).Person responsible for work
Industrial vacuum cleaner, dust class H, will be made availableEmployer
Ensure adequate aeration and ventilation.Person responsible for work
Protective work gear, disposable protective suits with hoods, acid-proof protective gloves, disposable overshoes, safety goggles, protective helmets and respiratory protection (independent of the circulating air) must be provided.Employer
PPE must be used in accordance with the operating instructions.Employees
Restricted access zones set up with prohibitory sign D-P006 "Access prohibited for unauthorized persons" visibly mounted.Person responsible for work
Compliance with smoking, eating and drinking restrictionsEmployees
Compliance with restrictions related to work involving a significant heat build-upPerson responsible for work, all employees
A skin protection program is implemented in accordance with the skin protection planEmployer/all employees
Operating instructions are availableEmployer
Instruction and consultation on occupational medicine and toxicological mattersEmployer, annually
Occupational medical precautions are organized as a result of the risk assessment and in compliance with the ArbMedVV. Preventive medical data is being collected and maintainedEmployer/Company physician
Appropriate containers are available for the collection of used PPE as well as contaminated resources, including switching dust, to ensure their proper disposal.Employer, Employees
Applied directives, regulations and information

German Ordinance on Hazardous Substances (Gefahrstoffverordnung, GefStoffV)

TRGS 400 German Technical Rule for Hazardous Substances "Risk assessment for activities involving hazardous substances" (Gefährdungsbeurteilung für Tätigkeiten mit Gefahrstoffen).

TRGS 401 German Technical Rule for Hazardous Substances "Risks resulting from skin contact - identification, assessment, measures" (Gefährdung durch Hautkontakt - Ermittlung. Beurteilung, Maßnahmen)

DGUV Information "SF6 Switchgear and Equipment" ("SF6 -Anlagen und -Betriebsmittel", DGUV Information 213-013)

Technical Report IEC 62271-303, Annex D

g_bu_2075_as_1.jpgBG ETEM
Energie Textile Elektro
Medienerzeugnisse
Risk assessment - DocumentationClarification of faults in SF6 systems with gas leakage

Please note:Entries in italics are sample texts that you can edit to meet your needs.

Dokumentation
Prepared by: ......................... Responsible Person: .........................
Status as of: ......................... Expert consultation: .........................
Work area:Electrical service location
Work task:Clarification of faults in SF6 systems with gas leakage
Description of work tasks

In the course of a fault report, the switchgear room must be entered by an employee to clarify the fault. The switchgear must be inspected and the extent of the fault determined.

Hazardous substances used/released
DesignationLabelling / H statementsQuantity
SF6Gases under pressure, liquefied gas; H280The volume released will depend on the malfunction
Gaseous and solid decomposition productsDecomposition products can be poisonous, causing a hazard to health, irritation or chemical burnsThe volume released will depend on the malfunction
Assessment

Risk due to inhalation

The inhalation of SF6 and SF6 decomposition products cannot be excluded. For this reason, the short-term exposure may be greater than the working limit value.

Inhalation can lead to a health risk and result in damage to the lungs.

Risk due to contact with the skin

Contact with skin may cause irritation or chemical burns. There is a moderate risk from skin contact according to TRGS 401.

Physical-chemical and other hazards

A risk of suffocation may ensue due to a displacement of oxygen if a residual quantity of SF6 escapes from the switchgear into the working environment.

Protective measures/Effectiveness
Protective measures/checkpointsResponsibility (deadline)Effectiveness/verification
Determining the criteria for remedying malfunctions in accordance with the extent of the damageEmployer/Person responsible for work
All activities that are not related to fault clearance are prevented.Person responsible for work
Ensure adequate aeration and ventilation.Person responsible for work
Protective work gear, disposable protective suits with hoods, acid-proof protective gloves, disposable overshoes, safety goggles, protective helmets and respiratory protection (independent of the circulating air) are be provided.Employer
PPE appropriate to the fault is used in accordance with instructions from the superior.Employees
Restricted access zones are set up with prohibitory sign D-P006 "Access prohibited for unauthorized persons" visibly mounted.Person responsible for work
Compliance with smoking, eating and drinking restrictionsEmployees
Operating instructions are availableEmployer
Instruction and consultation on occupational medicine and toxicological mattersEmployer, annually
Occupational medical precaution is organized as a result of the risk assessment and in compliance with the ArbMedVV. Preventive medical data is being collected and maintainedEmployer/Company physician
Applied directives, regulations and information

German Ordinance on Hazardous Substances (Gefahrstoffverordnung, GefStoffV)

German Ordinance on occupational health precautions (Verordnung zur arbeitsmeidizinischen Vorsorge, ArbMedVV)

TRGS 400 German Technical Rule for Hazardous Substances "Risk assessment for activities involving hazardous substances" (Gefährdungsbeurteilung für Tätigkeiten mit Gefahrstoffen).

TRGS 401 German Technical Rule for Hazardous Substances "Risks resulting from skin contact - identification, assessment, measures" (Gefährdung durch Hautkontakt - Ermittlung. Beurteilung, Maßnahmen)

DGUV Information "SF6 Switchgear and Equipment" ("SF6-Anlagen und -Betriebsmittel", DGUV Information 213-013)

Technical Report IEC 62271-303, Annex D